MGE UPS Systems EX 7RT Power Supply User Manual


 
Table 3-3: ON/OFF features.
Display Factory setting Options Comments
Cold start Disabled Enabled Start on battery.
Forced reboot Enabled Disabled Enables automatic restart of
the system even if normal AC
source is restored before the
end of the shutdown sequence.
Automatic restart Enabled Disabled UPS restarts automatically
when normal AC source
is restored.
Sleep mode Disabled Enabled Automatic shutdown on battery
if output load level <10%
Remote Command Enabled Disabled Enables shutdown or restart
orders from software.
Table 3-4: Battery features.
Display Factory setting Options Comments
Battery test Every week No test/daily/monthly
Pre-Alarm 20% 0 to 100% Low battery signal;1% increment
Runtime choice UPS reads # and type From 65 to 400 Ah Requires EX 5/7/11RT CLA if
of battery using options (see section 1.5.4
modules connected. “Battery extensions cable kit”)
Battery deep discharge Enabled Disabled If disabled, loss of
protection MGE UPS SYSTEMS,INC.
warranty.
3.2.2 Accessing personalization through external software
Insert the Solution-Pac CD ROM in your CD drive.
At the first Navigator Screen, select "Installation" and follow the instructions to install Personal
Solution-Pac for Windows.
If nothing appears, launch startup.exe
Then go to "Advanced settings" and "UPS settings".
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.
3.2.3 Final startup sequence
Press the <ON> button more than 3 seconds.
After UPS internal test sequence, the green LED goes on.
CAUTION During the restart, if the Bypass AC source is out of
tolerance, the UPS will generate an output
calibrated 10 msec output interrupt.
15
EX 5/7/11 RT System
Operation3 — 4 86-86000-00 A01