Minuteman UPS ED6000T Power Supply User Manual


 
20
3.6.1.6 The UPS will perform another self-test and the LCD display will change
from drawing C to drawing D. During the self-test the UPS will switch to
the Battery mode for approximately 4-seconds, then the LCD display will
change from drawing D to drawing E1. Once the UPS successfully passes
the self-test the LCD will display drawing F. If the UPS fails the self-test the
LCD will display drawing E2 then the LCD will display an error code or
error status. See Section 2.2 for Error codes and Section 4 for
Troubleshooting.
D
* It shows “test” during the self-test.
E1
* It shows “OK” if the self-test was successful.
E2
* It shows “Fail” if the UPS fails the self-test.
F
* It shows “208VAC” Utility Input.
21
3.6.1.7 The UPS has successfully passed the start-up procedure. The UPS will
charge the batteries whenever the UPS is connected to an AC source and
there is an acceptable AC voltage present. It is recommended that the
UPS's batteries be charged for a minimum of 8-hours before use. However
the UPS may be used immediately, but the “On-Battery” runtime maybe
less than normally expected. NOTE: If the UPS is going to be out of
service or stored for a prolonged period of time, the batteries must be
recharged for at least 12-hours every 3 months.
3.6.2 Startup in Battery Mode (Cold Start)
3.6.2.1 Switch the UPS’s input circuit breaker (on the rear panel) to the On
position.
3.6.2.2 Press and hold the UPS On Switch (on the front panel)
for
approximately 3-seconds, then release, the audible alarm will sound 2-
beeps. The LCD display will scroll from drawing A to drawing G this will
take approximately 10-seconds.
3.6.2.3 During this 10-seconds press and hold the UPS On Switch again
for
approximately 3-seconds, then release, the audible alarm will sound 2-
beeps. The LCD display will change from drawing G to drawing H, the
UPS will be in self-test mode. The UPS will provide an output within
approximately 1-minute, and then the LCD display will display drawing I. If
the UPS On switch was not pressed within the 10-seconds, the UPS will
automatically turn off. You will have to repeat the above steps again.
G
* It shows “Off”, which means the UPS pre-start is successful.
H
* It shows the Utility input is “0VAC”.