MITSUBISHI ELECTRIC 2033C SERIES UPS
MITSUBISHI
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-7
FIGURE 1.3 Single Line Diagram - Battery Operation
The UPS is equipped with an internal rotary type Maintenance Bypass Switch (MBS) that can be
used to divert utility power to the load during maintenance sessions. Figure 1.4 illustrates the power
path when the MBS is in the BYPASS mode.
FIGURE 1.4 Single Line Diagram - UPS on Maintenance Bypass Operation.
(7.5/10/15/20kVA)
The rotary maintenance bypass switch is shown as 52CS in Figure 1.4. 52CS is a two position
three point make-before-break transfer switch.
(30/40/50kVA)
Two contactors (52MB, 52L) are used instead of the 52CS. A rotary switch(SWM) is used for
control of the two contactors.