Mitsubishi Electronics 9800A SERIES Power Supply User Manual


 
MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
1-13
1.4 Specifications
The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.
TABLE 1.1 Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 4 wire
Output voltage
3 phase / 3 or 4 wire
100kVA / 80kW
150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW
480V
480V
480V
480V
480V
480V
480V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
TABLE 1.2 UPS Module Information
UPS
[kVA]
CABLE
ENTRY
WIDTH
[in / mm]
DEPTH
[in / mm]
HEIGHT
[in / mm]
WEIGHT
[lb./ kg]
HEATING
[kBTU/h]
100 BOTTOM 43.3 / 1100 29.8 / 758 79.7 / 2025 2100 / 950 22.0
150 BOTTOM 47.2 / 1200 29.8 / 758 79.7 / 2025 2820 / 1275 33.0
225 BOTTOM 55.1 / 1400 29.8 / 758 79.7 / 2025 3310 / 1500 45.0
300 TOP 76.8 / 1950 37.7 / 958 79.7 / 2025 4990 / 2260 68.0
375 TOP 76.8 / 1950 37.7 / 958 79.7 / 2025 5250 / 2380 84.0
500 TOP 114.2 / 2900 37.7 / 958 79.7 / 2025 6930 / 3140 98.0
750 TOP 129.9 / 3300 49.5 / 1258 79.7 / 2025 9655 / 4380 136.1