Mitsubishi Electronics 9800A SERIES Power Supply User Manual


 
MITSUBISHI ELECTRIC 9800A SERIES UPS
Page Number:
3-26
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
C) Bypass Operation Procedure
UPS-1
1. Check for “SYNC” on the LCD.
2. Press the "START/STOP MENU" from the LCD Main Menu.
3. Press the "STOP" key on the LCD.
Next UPS
Stop the next UPS in the same way as UPS-1.
The paralleling UPS system will be in bypass operation when all inverters stop.
** Transfer from bypass to inverter.
UPS-1
1. Press the "START/STOP MENU" from the LCD Main Menu.
2. Press the "START" key on the LCD.
Next UPS
Start the next UPS in the same way as UPS-1.
The paralleling UPS system will be in inverter operation when all inverters start.
Note: When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter
start or stop operation can only be performed remotely. If local inverter start or stop operation
is required (at the UPS), select "LOCAL" in "Remote/Local" selection in setup page. Select
“LOCAL” mode for the purpose of this stop procedure.