. 8 discrete isolated inputs
. 24 V dc field voltage sources
. User definable input threshold
. Pulse counting option
Module Specications
Inputs
Number of channels ...........................................................................8
OFF voltage...........................................................................< 3.2 V dc
ON voltage .............................................................................> 11 V dc
Wetting current ........................................6.3 mA (nom.) @ 24 V dc
Minimum pulse width detected ...............................................3 ms
Maximum switching frequency (no-filtering)....................200 Hz
Maximum voltage
Input ......................................................................................30 V dc
Reverse input....................................................................– 25 V dc
Congurable Parameters
Selectable input filter ...........................fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs................................................................enable /disable
Latch polarity......................................latch on high / latch on low
Pulse counting ..........................................................enable /disable
Response Time
I/O response time
Field event to new data available on Railbus............3 ms (max.)
Safety
FM non-incendive field wiring parameters (each channel)
........................V
max
= 30 V; I
max
= 100 mA; C
i
= 0 μF; L
i
= 0 mH
Power Supplies
Railbus (12V) current......................................................35 mA (typ.)
...........................................................................................55 mA (max.)
Bussed Field Power .......................................................not required
NT-8109-DI-DC
Image Description
8-channel Discrete Input
24 V dc, isolated, sinking
Mechanical
Module Key Code..............................................................................B2
Module width ............................................................................42 mm
Weight............................................................................................170 g
Field Terminals
Field Wiring Recommended
Field Terminal
Compatible
Field Terminal
General Purpose NT-8602-FT-ST
Standard †
NT-8604-FT-FU
Fused
Class 1, Div 2
or Zone 2 hazard-
ous area
NT-8601-FT-NA
Non-arcing †
NT-8611-FT-FU
Non-arcing,
Fused
† External fusing of the Field Power supply is recommended
in order to protect the field wiring.
NovaTech 8000 Series I/O Family
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks
are properties of their respective owners. NovaTech is a registered
trademark of NovaTech, LLC. The information in this literature is
subject to change without notice and is not to be construed as a
warranty. DS_8109_0607