NotaTech 8000SeriesI/O Switch User Manual


 
18
Contact:
®
NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD 21117
T: 410.753.8300
Toll Free: 800.253.3842
www.novatechweb.com
. 8 discrete inputs for dry contact switches
. 24 V dc provided on input high side
. Returns commoned internally
. Pulse counting option
. 24 V dc bussed field power required
Module Specications
Inputs
Number of channels ...........................................................................8
OFF current ..........................................................................< 0.69 mA
ON current............................................................................> 2.24 mA
Wetting current .................................................................5 mA (typ.)
Minimum pulse width detected ...............................................3 ms
Maximum switching frequency (no-filtering)....................200 Hz
Isolation (any channel to Railbus) .....................................250 V ac
Congurable Parameters
Selectable input filter ...........................fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs................................................................enable /disable
Latch polarity......................................latch on high / latch on low
Pulse counting ..........................................................enable /disable
Response Time
I/O response time
Field event to new data available on Railbus............3 ms (max.)
Safety
FM non-incendive field wiring parameters (each channel)
...................V
oc
= 30 V; I
sc
= 15.2 mA; C
a
= 0.12 μF; L
a
= 151 mH
Power Supplies
Railbus (12V) current......................................................35 mA (typ.)
...........................................................................................55 mA (max.)
Bussed Field Power ......................................40 mA, @ 18—36 V dc
NT-8110-DI-DC
Image Description
8-channel Discrete Input
24 V dc, non-isolated, module powered
Mechanical
Module Key Code..............................................................................B1
Module width ............................................................................42 mm
Weight............................................................................................170 g
Field Terminals
Field Wiring Recommended
Field Terminal
Compatible
Field Terminal
General Purpose NT-8602-FT-ST
Standard †
NT-8604-FT-FU
Class 1, Div 2
or Zone 2 hazard-
ous area
NT-8601-FT-NI
Non-incendive †
NT-8603-FT-FU
Non-incendive,
fused
† External fusing of the field power supply is recommended
in order to protect the field wiring.
NovaTech 8000 Series I/O Family
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks
are properties of their respective owners. NovaTech is a registered
trademark of NovaTech, LLC. The information in this literature is
subject to change without notice and is not to be construed as a
warranty. DS_8110_0607