. 8 powered outputs
. Controls solenoids and relays
. Common load supply of up to 60 V dc
. Discrete or pulsed outputs
. 1A per channel switched current
. 2–60 V dc bussed field power required
Module Specications
Outputs
Number of channels ...........................................................................8
Output voltage range.........................................................2–60 V dc
ON voltage drop.............................................................0.25 V (max.)
OFF leakage current ...................................................1.0 mA (max.)
Switched current per channel ††
Continuous *................................................................................1 A
For < 100 ms.................................................................................4 A
For < 20 ms...................................................................................6 A
Congurable Parameters
Output initialization state....................................predefined
value
Fail-safe.................................................predefined value/last value
Output .....................discrete, momentary or continuous pulse‡
Pulse width.....................................................................2 ms to 130 s
Response Time
Response time
From Railbus command to output change ..........1 ms (max.)
Power Supplies
Railbus (12V) current......................................................45 mA (typ.)
...........................................................................................70 mA (max.)
Bussed Field Power .........................................................2 to 60 V dc
NT-8115-DO-DC
Image Description
8-channel Discrete Output
2–60 V dc, non-isolated, module powered
Mechanical
Module Key Code..............................................................................B6
Module width ............................................................................42 mm
Weight............................................................................................200 g
Field Terminals
Field Wiring Recommended
Field Terminal
Compatible
Field Terminal
General Purpose NT-8604-FT-FU
Fused
NT-8602-FT-ST
Standard †
Class 1, Div 2
or Zone 2 hazard-
ous area
NT-8611-FT-FU
Non-arcing,
Fused
NT-8610-FT-NA
Non-arcing †
† Alternative fusing in the field wiring is recommended if it is
not provided in the field terminal.
†† The total instantaneous switched current should not
exceed the following:
10 A for < 100 ms
18 A for < 20 ms
*Limited to 6 A per module
‡Consult NovaTech for availability