Omron CJ1W-CLK21-V1 Network Card User Manual


 
49
Component Names and Functions Section 3-1
3-1-3 C200HX/HG/HE Controller Link Unit
Wired Unit Indicators
1
Indicators
LED indicators that display the Unit and network status.
Node address switches
Two rotary switches. The node address of the Unit on the
Controller Link Network is set in 2-digit decimal.
Baud rate and operating level settings
A four-pin DIP switch. The following settings are made.
Pins 1, 2: Baud rate
Pin 3: Not used (leave set to OFF)
Pin 4: Operating level
Bus Connection Unit Connector
Connector used for connection to the CPU Unit.
Terminal block for the communications cable
Terminals to connect to the Controller Link Network communications
cable (twisted-pair cable).
Terminating resistance switch (underneath the Unit)
A slide switch. Use this switch to set the terminating resistance to ON for
nodes at both ends of the Controller Link Network.
CLK21
NODE NO.
X10
1
X10
0
SW1
ON
BD H
BD L
SHLD
RUN
ERC
INS
SD
TER
ERH
M/A
LNK
RD
TER
SW
#0, #1
1
2
3
4
RSV
BAUD
RATE
01
ON
234
(Refer to p. 49 and 276)
(Refer to p. 94)
(Refer to p. 95)
(Refer to p. 59)
(Refer to p. 66)
(Refer to p. 96)
Name Color Status Meaning
RUN
(operating)
Green Lit Unit operating normally.
Not lit Unit error.
TER
(terminating
resistance)
Yellow Lit Terminating resistance switch ON.
Not lit Terminating resistance switch OFF.
ERC (communica-
tions error)
Red Lit Communications error, node address
setting error (same address set twice), or
hardware error.
Not lit Normal operation
ERH
(PLC error)
Red Lit PLC error, PLC interface error, EEPROM
error, or PLC model setting error.
Not lit No error.
INS
(network
participation)
Yellow Lit Unit is participating (inserted) in the net-
work.
Not lit Unit is not participating (inserted) in the
network.
M/A
(data link mode)
Yellow Lit Manual
(see note)
Note:
M/A is always not lit
when data links are not
active in the network.
Not lit Automatic
LNK
(data link)
Yellow Lit Data links participating.
Flashing Error in data link table.
Not lit Not in a data link or data link inactive.
SD
(send)
Yellow Lit Data transmission.
Not lit No data transmission.