31
Special I/O Units and CPU Bus Units
Process I/O Units ■
Isolated-type Units with Universal Inputs ●
Unit
classification
Product
name
Input
points
Signal
range
selection
Signal range
Conversion
speed
(resolution)
Accuracy
(at ambient
temperature of
25°C)
External
connection
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
5 V 24 V
CJ
Special
I/O
Units
Process
Input
Units
(Isolated-
type
Units
with
Universal
Inputs)
4
inputs
Set
separately
for each
input
Universal inputs:
Pt100 (3-wire),
JPt100 (3-wire),
Pt1000 (3-wire),
Pt100 (4-wire), K,
J, T, E, L, U, N, R,
S, B, WRe5-26, PL
II, 4 to 20 mA, 0 to
20 mA, 1 to 5 V,
0 to 1.25 V, 0 to 5
V, 0 to 10 V, ±100
mV selectable
range −1.25 to
1.25 V, −5 to 5 V,
−10 to 10 V, ±10 V
selectable range,
potentiometer
Resolution
(conversion
speed):
1/256,000
(conversion
cycle: 60 ms/
4 inputs)
1/64,000
(conversion
cycle: 10 ms/
4 inputs)
1/16,000
(conversion
cycle: 5 ms/
4 inputs)
Standard
accuracy: ±0.05%
of F.S.
Removable
terminal
block
1
0.30 — CJ1W-PH41U UCI, CE
4
inputs
Set
separately
for each
input
Universal inputs:
Pt100, JPt100,
Pt1000, K, J, T,
L. R, S, B, 4 to
20 mA,
0 to 20 mA, 1 to
5 V, 0 to 5 V, 0 to
10 V
Conversion
speed:
250 ms/
4 inputs
Accuracy:
Platinum
resistance
thermometer
input: (±0.3% of
PV or ±0.8°C,
whichever is
larger) ±1 digit
max.
Thermocouple
input: ±0.3% of
PV or ±1.5°C,
whichever is
larger) ±1 digit
max. (See note.)
Voltage or current
input: ±0.3% of
F.S. ±1 digit max.
.032 — CJ1W-AD04U UCI, CE
Note: L and −100°C or less for K and T are ±2°C±1 digit max., and 200°C or less for R and S is ±3°C±1 digit max. No accuracy is specified for 400°C or less for B.
Isolated-type Thermocouple Input Units ●
Unit
classification
Product
name
Input
points
Signal
range
selection
Signal range
Conversion
speed
(resolution)
Accuracy
(at ambient
temperature
of 25°C)
External
connection
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
5 V 24 V
CJ
Special
I/O
Units
Process
Input
Units
(Isolated-
type
Thermo-
couple
Input
Units)
2
inputs
Set
separately
for each
input
Thermocouple:
B, E, J, K, L, N, R,
S, T, U, WRe5-26,
PLII
DC voltage:
±100 mV
Conversion
speed:
10 ms/
2 inputs,
Resolution:
1/64,000
Standard
accuracy:
±0.05% of F.S.
(See note 1.)
Removable
terminal
block
1
0.18
0.06
(See
note
2.)
CJ1W-PTS15
UC1, CE
4
inputs
Thermocouple:
R, S, K, J, T, L, B
Conversion
speed:
250 ms/
4 inputs
Accuracy:
(±0.3% of PV or
±1°C,
whichever
is larger) ±1
digit max.
(See note 3.)
0.25 — CJ1W-PTS51
Note 1. The accuracy depends on the sensors used and the measurement temperatures. For details, refer to the user’s manual.
2. This is for an external power supply, and not for internal current consumption.
3. L and −100°C or less for K and T are ±2°C±1 digit max., and 200°C or less for R and S is ±3°C±1 digit max. No accuracy is specified for 400°C or less for B.
Ordering Information