Ordering Information
Analog Output Units
Unit
classification
Product
name
Output
points
Signal
range
selection
Signal
range
Resolution
Conversion
speed
Accu-
racy (at
ambient
temper-
ature of
25°C)
External
connection
External
power
supply
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
5 V 24 V
CJ
Special
I/O
Units
Analog
Putput
Units
8
outputs
Set
separately
for each
input
1 to
5 V,
0 5 to
5 V,
0 to 10
V,
−10 to
10 V
1/4,000
(Settable
to
1/8,000)
1 ms/ point
max.
(Settable to
250
μs/point)
±0.3% of
F.S.
Removable
terminal
block
24
VDC
+10%
–15%,
140 mA
max.
1
0.14
0.14
(See
note.)
CJ1W-
DA08V
UC1, N, L,
CE
8
outputs
4 to 20
mA
24
VDC
+10%
–15%,
170 mA
max.
0.14
0.17
(See
note.)
CJ1W-
DA08C
UC1, N,
CE
4
outputs
1 to
5 V,
0 to
5 V,
0 to 10
V,
−10 to
10 V,
4 to 20
mA
1/4000
1 ms/ point
max.
Voltage
output:
±0.3% of
F.S.
Current
output:
±0.5% of
F.S.
24
VDC
+10%
–15%,
200 mA
max.
0.12
0.2
(See
note.)
CJ1W-
DA041
UC1, N, L,
CE
2
outputs
24
VDC
+10%
–15%,
140 mA
max.
0.12
0.14
(See
note.)
CJ1W-
DA021
Note: This is for an external power supply, and not for internal current consumption
Analog I/O Units
Unit
classification
Product
name
No. of
points
Signal
range
selection
Signal
range
Resolution
(See note.)
Conversion
speed
(See note.)
Accuracy
(at ambient
temperature
of 25°C)
External
connection
No. of
unit
numbers
allocated
Current
consumption
(A)
Model Standards
5 V 24 V
CJ
Special
I/O
Units
Analog
I/O
Units
4 inputs
Set
separately
for each
input
1 to 5
V,
0 to 5
V,
0 to
10 V,
−10 to
10 V,
4 to
20
mA
1/4,000
(Settable
to
1/8,000)
1 ms/point
(Settable to
500 μs/
Voltage input:
±0.2% of F.S.
Current input:
±0.2% of F.S.
Removable
terminal
block
1 0.58
CJ1W-
MAD42
UC1, N, L,
CE
2
outputs
Voltage output:
±0.3% of F.S.
Current output:
±0.3% of F.S.
Note: The resolution and conversion speed cannot be set independently. If the resolution is set to 1/4,000, then the conversion speed will be 1 ms/point.