Klinkmann Automation Omron Ethernet DAServer 23
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14
This configuration view has 15 parameters (configuration requires proven network
information, it can not be validated by the DAServer):
• Enter Controller’s Network Address - to each network in the OMRON system
can be assigned an unique network address between 0 and 127. When
communicating with a node on another (remote) network, the entered value must
be consistent with the network address (non-zero) assigned in the routing tables.
The network address of 0 indicates the local network. Note: The default Network
Address is 0.
• Enter Controller’s Node Address - each OMRON Controller in Ethernet network
must have its own unique node address between 1 and 126 (if Controller is inter-
networked via other OMRON FA network then Node Address can have different
range. For example, if inter-networked via SYSMAC LINK network, the Node
Address range is between 1 and 62. Care should be taken to select a node
address that will not conflict with other devices in the system.
Note: If destination node is OMRON PLC with Ethernet Unit installed then Controller
Node Address must be configured according to following rules:
- if automatic conversion of Ethernet Unit’s IP address is used
(also the node number
setting rotary switch on the front panel of the Ethernet Unit is used) then Controller
Node Address must be equal with the fourth byte (octet) of local IP address of
Ethernet Unit;
- if automatic conversion of Ethernet Unit’s IP address is not used
(IP Address Table
is used) then Controller Node Address must be equal with the Node number
configured in the Ethernet Unit’s IP Address Table.
• Enter Controller’s IP Address. The Controller’s IP Address must match with IP
address configured at corresponding controller Ethernet Unit system setup.
• Enter Controller’s Port Number. Enter the UDP Port Number used for
communications with this OMRON controller. The Port Number must much with the
Port Number set in the OMRON controller by appropriate Ethernet Unit
configuration software. Note: The default port number is 9600.
• Enter Computer’s Network Address - the Local Network Address: the unique
network address between 1 and 127 is assigned to each OMRON Ethernet
network in the system. The entered value must be consistent with the network
address assigned in the routing tables. When communicate only with nodes in the
local network, you can set this Address to zero (default value).
• Select the Controller Series. The available series are: CS1/CJ1, C200HX/HG/HE,
CV-series, C/CPM2X and CQM1. To select Controller Series, click on the combo
box button and make your choice from the list. Note: Only PLCs of CS1/CJ1,
C200HX/HG/HE and CV series are directly accessible in Ethernet network. All
other series PLCs must be inter-networked to get data from them.
• Select Controller type. To select Controller type, click on the combo box button
and make your choice from the list. The available types depends on selection in
Controller Series combo box: CS1/CJ1 series offers 2 options (CS1 and CJ1),
C200HX/HG/HE series offers one option (C200HX/HG/HE), CV-series offers 5
options (CV500, CVM1-CPU01-E, CV1000, CV2000 and CVM1-CPU11-E),