Klinkmann Automation Omron Ethernet DAServer 62
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14
operation manual)
04 Node number setting
error.
Make sure the node
number is within
specified range and that
there are no duplicate
node numbers.
DASProtFail
04: Not
executable
01 An undefined
command has been
used, or short frame (4
bytes) is being used for
FINS header frame.
Check the command
code and be sure code
is supported by Unit to
which command is
sent.(*)
DASProtFail
05: Routing
error
01 Destination node
number is not set in the
routing tables.
Set the remote PLC in
the routing tables.
DASProtFail
02 Routing tables aren't
registered.
Set the the routing
tables at the relay nodes
and remote node.
DASProtFail
03 Routing table error. Set the the routing
tables correctly.
DASProtFail
04 The maximum number
of relay nodes (2) was
exceeded in the
command.
Redesign the network to
reduce number of relay
nodes.
DASProtFail
10:
Command
format error
01 The command is longer
than the max.
permissible length.
Check the command
format and set it
correctly.(*)
DASProtFail
02 The command is
shorter than the min.
permissible length.
Check the command
format and set it
correctly.(*)
DASProtFail
03 The designated
number of data items
differs from the actual
number.
Check the number of
items and data and
make sure that they
agree.(*)
DASProtFail
05 An incorrect header
has been used. (Data
for another node was
received. Attempt was
made to send response
to broadcast address)
Check the header
parameters in the
command and be sure
the correct command
format is used.(*)
DASProtFail
11:
Parameter
error
00 The parameter in the
command data were
incorrect or the
Check the parameters
and be sure the socket
number is between 1
DASProtFail