Pelco REL2064 Network Card User Manual


 
C1518M-A (11/02) 11
2. Set the DIP switches.
Figure 7. SW1 DIP Switches
DIAGNOSTICS:
OFF
LOCAL DEVICE ADDRESS
ON
1
2
3
4
5
6
7
8
9
10
NOT USED:
OFF
DEFAULT SETTINGS: LOCAL DEVICE ADDRESS 1,
DIP SWITCH 9 OFF,
DIP SWITCH 10 ON
00697
NOT USED:
OFF
MEMORY (MEM) CONTACTS
1-16: OFF OR ON
17-32: OFF OR ON
33-48: OFF OR ON
49-64: OFF OR ON
NOT CONNECTED:
OFF
MEM ON: SETTINGS REMAIN IN MEMORY IN CASE OF POWER
FAILURE OR ACCIDENTAL RESET
MEM OFF: SETTINGS GO BACK TO THE FACTORY DEFAULT IN
CASE OF POWER FAILURE OR ACCIDENTAL RESET
ON
1
2
3
4
5
6
7
8
9
10
DEFAULT SETTINGS: MEMORY FEATURE DISABLED,
DIP SWITCHES 1, 2, AND 7-10 OFF
00698
BAUD RATE
1200: OFF, OFF, OFF
2400: ON, OFF, OFF
4800: OFF, ON , OFF
9600: ON, ON, OFF
19200: OFF, OFF, ON
38400: ON, OFF, ON
57600: OFF, ON, ON
115200: ON, ON, ON
BEGIN RELAY RANGE/BEGIN GPI
1-64/1: OFF, OFF, OFF
65-128/9: ON, OFF, OFF
129-192/17: OFF, ON, OFF
193-256/25: ON, ON, OFF
257-320/33: OFF, OFF, ON
321-384/41: ON, OFF, ON
385-448/49: OFF, ON, ON
449/57: ON, ON, ON
RELAY CONTACT GROUPS
7 (1-16): OFF (N.O.) ON (N.C.)
8 (17-32): OFF (N.O.) ON (N.C.)
9 (33-48): OFF (N.O.) ON (N.C.)
10 (49-64): OFF (N.O.) ON (N.C.
)
N.O. = NORMALLY OPEN
N.C. = NORMALLY CLOSED
SUP = SUPERVISED
UNSUP = UNSUPERVISED
ON
1
2
3
4
5
6
7
8
9
10
DEFAULT SETTINGS: BAUD 19200, RELAY RANGE 1-64,
RELAY CONTACT GROUPS N.O.
NOTE: REFER TO APPENDIX A FOR EACH LOCAL DEVICE
ADDRESS (1-253).
Figure 8. SW2 DIP Switches
Figure 9. SW3 DIP Switches
3. Replace the front panel.