Powerware 3110 Power Supply User Manual


 
Specifications
14
Powerware
®
3110 User's Guide S LTM-XXXX A Draft 03/01/2001
Table 3. Battery
Configuration 250 VA: (1) 12V or (2) 6V, 4.2 Ah internal battery(s)
425 VA: (1) 12V, 7 Ah internal battery
600 VA: (1) 12V, 9 Ah internal battery
Voltage 12 Vdc
Type Sealed, maintenanceĆfree, valveĆregulated, leadĆacid
Charging 8 hours to 95% capacity with output fully loaded
Monitoring Advanced monitoring for earlier failure detection and warning
Backup Time 250-425 VA: 3 minutes at full load; 5 minutes typical load
600 VA: 2.5 minutes at full load; 5 minutes typical load
Transfer Time 4 ms typical
Table 4. Weights and Dimensions
UPS Dimensions
(HxWxD)
250 VA: 15.0 x 5.9 x 39.3 cm (5.9" x 2.3" x 15.5")
425-600 VA: 17.2 x 7.9 x 37.6 cm (6.8" x 3.1" x 14.8")
UPS Weight 250 VA: 3.0 kg (6.6 lb)
425 VA: 4.2 kg (9.2 lb)
600 VA: 4.3 kg (9.4 lb)
Table 5. Environmental and Safety
120V Model 230V Model
Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature -15°C to 50°C (-5°F to 122°F)
If the UPS is stored, the batteries should be recharged every 6 months. If stored above 25°C
(77°F), battery life is reduced and should be recharged more often.
Ventilation Air around the unit must be free of dust, chemicals, or other materials
that corrode or contaminate.
Relative Humidity 5ć95% RH noncondensing
Audible Noise Less than 40 dBA typical at one meter
Surge Energy Rating 450 joules
Surge Suppression ANSI C62.41 Category A (formerly IEEE 587) IEC 61000-4-5, Level 3
Safety Conformance UL 1778; UL 497A;
CAN/CSA C22.2, No. 107.1
EN 50091-1-1 and IEC 60950
Safety Markings UL, cUL TUV/GS, CE
EMC (Class B) FCC Part 15, ICES-003 EN 50091-2