Powerware FCC 15 Network Card User Manual


 
INTEGRATING THE UPS
EATON Powerware
®
Modbus
®
Card User’s Guide S 164201376 Rev C www.powerware.com
21
Table 5. Read Input Registers - Modbus Function Code 04 (Input Registers Start at 30000)
Register Meter Name Scale Unit
1 OUTPUT VOLTS AB /10 Volts
2 OUTPUT VOLTS BC /10 Volts
3 OUTPUT VOLTS CA /10 Volts
4 INPUT VOLTS AB /10 Volts
5 INPUT VOLTS BC /10 Volts
6 INPUT VOLTS CA /10 Volts
10 BYPASS VOLTS AB /10 Volts
11 BYPASS VOLTS BC /10 Volts
12 BYPASS VOLTS CA /10 Volts
19 INPUT CURRENT PHASE A /10 Amps
20 INPUT CURRENT PHASE B /10 Amps
21 INPUT CURRENT PHASE C /10 Amps
22 OUTPUT TRUE POWER /10 kW
23 INPUT TRUE POWER /10 kW
24 OUTPUT APPARENT POWER /10 kVA
25 INPUT APPARENT POWER /10 kVA
26 OUTPUT POWER FACTOR /100
27 INPUT POWER FACTOR /100
28 OUTPUT FREQUENCY /10 Hz
29 INPUT FREQUENCY /10 Hz
30 INVERTER FREQUENCY /10 Hz
31 BYPASS FREQUENCY /10 Hz
33 BATTERY CURRENT /10 Amps
34 BATTERY VOLTAGE /10 Volts
35 % BATTERY LEFT /10 %
36 BATTERY TIME R EMAINING /10 Minutes
60 INVERTER VOLTS PHASE A /10 Volts
61 INVERTER VOLTS PHASE B /10 Volts