Table 7. Environmental and Safety
120V Models 230V Models
Operating Temperature 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Storage Temperature -20°C to 60°C (-4°F to 140°F)
Relative Humidity 5-95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Audible Noise Less than 45 dBA typical
Surge Suppression IEEE 587/ANSI C62.41 Category B
Safety Conformance UL 1778; CAN/CSA C22.2, No. 107.1 UL 1778; CAN/CSA C22.2, No. 107.1;
EN 50091-1 and IEC 60950
Safety Markings UL, CSA UL, CSA, CE
EMC FCC, VCCI EN 50091-2
Table 8. Indicators and Controls
Serial Communication Intelligent serial communication to provide alarms with history, measured parameters, self-test,
and many other features; contact your authorized dealer for UPS/computer communication
software options
Interface Ergonomic Indicators: Wiring Fault, Battery Service, Communication, Operation, System Normal
Bar Graphs: Input Level, Battery Charge Level, % Load
Contact Closures AC Input Failure, Low Battery
Table 9. Battery
120V Models 230V Models
Configuration 1000-1500 VA: internal batteries
2000-3000 VA: external PW5119 1048BP
1000-1500 VA: internal batteries
2000-3000 VA: external PW5119 1748BP
Voltage 24 Vdc for internal; 48 Vdc for external
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Advanced charging for faster recovery; approximately 4 hours to 90% usable capacity at nominal
line and no supplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning