Powerware 5125 Network Card User Manual


 
Specifications
41
Powerware
®
5125 Tower (1000–2200 VA)User’sGuide RevB www.powerware.com
Table 6. Environmental and Safety
Low Voltage Models High Voltage Models
Operating Temperature 10°C to 40°C (50°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Transit Altitude Up to 15,000 meters above sea level
Audible Noise Less than 40 dBA Normal mode, typical load
Less than 55 dBA Battery mode
Surge Suppression ANSI C62.41 Category B (formerly IEEE 587), IEC 61000-4-5
Safety Conformance UL 1778, UL 497A;
CAN/CSA C22.2, No. 107.1;
NOM-019-SCFI
UL 1778, UL 497A (data line only);
CAN/CSA C22.2, No. 107.1;
EN 50091-1-1 and IEC 60950
Agency Markings UL, cUL, NOM UL andcUL; CE, C-Tick, LGA/GS, DEMKO
EMC FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003
Table 7. Battery
Configuration 1000 VA: (2) 24V, 9 Ah internal batteries
1500 VA: (4) 48V, 7 Ah internal batteries
2200 VA: (4) 48V, 12 Ah internal batteries
EBM Configuration PW5125 EBM-24: (8) 24V, 9 Ah batteries
PW5125 EBM-48: (8) 48V, 9 Ah batteries
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Internal battery: less than 3 hours to 90% usable capacity at nominal line voltage after full
load discharge
External battery: recharging at 80% load or less is recommended; no more than 16x discharge
time to90% usable capacity at nominal line voltage after full load discharge; an external
battery charger is recommended for faster recharge times when using more than 2 EBM
s.
Monitoring Advanced monitoring for earlier failure detection and warning; auto detection of additional
EBMs