Rackmount Solutions VA 10000 Power Supply User Manual


 
Chloride Active and E-Series UPS User Manual 23
Efficiency > 83%
Protection class IP 20
Cooling Fan
Noise level mains operation < 41 dBa < 41 dBa < 50 dBa < 50 dBa
Noise level battery operation < 45 dBa <45 dBa < 50 dBa <50 dBa
Operating temperature (ambient)
+ 50°F to +105°F (10°C to + 40°C)
recommended +59°F to +89°F (+15°C to + 32°C)
Storage temperature +5°F to +104°F (-15°C to +40°C)
Relative humidity 20% to 90%,non-condensation
Altitude
max. 10,000 ft. (3000m),
above 5,000 ft. (1500m) max ambient temperature = 95°F
(35 °C)
Mechanical Data
UPS
Weight - lbs. (kg) 28.6 (13) 35.3 (16) 75 (34) 75 (34)
Dimensions - HxWxD in. (mm)
8.9 x 5.7 x 16 (225 x 145 x
405)
13.8 x 7.9 x 18.5 (350 x 200
x 470)
Battery extension
Type None
BPActive
1000
BPActive
3000
BPActive
3000
Weight lbs (kg) None 42 (19) 106 (48) 106 (48)
Dimensions - HxWxD in. (mm) None
8.9 x 5.7 x
16
(225x145x4
05)
13.8 x 7.9 x 18.5
(350 x 200 x 470)
Signals
Visual LED-indication at the front side
Audible Acoustical alarm
Communications
RS232 interface
Alarm contacts +5V...+12 V
Signal input +5V...+12 V
Ethernet (optional)
Table 5. Chloride Active UPS North America
UPS Model Active 700 Active 1000 Active 2000 Active 3000