Raypak B6000 Network Card User Manual


 
21
R 10215 6 High Limit (0 = Normal, 1 = Alarm)
R 10216 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10217 8 Manual Override (0 = Normal, 1 = Alarm)
R 10218 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10219 10 No Pilot (0 = Normal, 1 = Alarm)
30045 40045 bit Boiler #2 Status Word Boiler #2
R 10225 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10226 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10227 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10228 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10229 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10230 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10231 6 High Limit (0 = Normal, 1 = Alarm)
R 10232 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10233 8 Manual Override (0 = Normal, 1 = Alarm)
R 10234 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10235 10 No Pilot (0 = Normal, 1 = Alarm)
30046 40046 bit Boiler #3 Status Word Boiler #3
R 10241 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10242 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10243 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10244 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10245 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10246 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10247 6 High Limit (0 = Normal, 1 = Alarm)
R 10248 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10249 8 Manual Override (0 = Normal, 1 = Alarm)
R 10250 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10251 10 No Pilot (0 = Normal, 1 = Alarm)
30047 40047 bit Boiler #4 Status Word Boiler #4
R 10257 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10258 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10259 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10260 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10261 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10262 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10263 6 High Limit (0 = Normal, 1 = Alarm)
R 10264 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10265 8 Manual Override (0 = Normal, 1 = Alarm)
R 10266 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10267 10 No Pilot (0 = Normal, 1 = Alarm)
30048 40048 bit Boiler #3 Status Word Boiler #5
R 10273 0 Boiler Not On Line (0 = Normal, 1 = Alarm)
R 10274 1 Boiler Operation (0 = Firing, 1 = Ready)
R 10275 2 Low Water Cutoff (0 = Normal, 1 = Alarm)
R 10276 3 Low Pressure Water (0 = Normal, 1 = Alarm)
R 10277 4 Low Pressure Gas (0 = Normal, 1 = Alarm)
R 10278 5 High Pressure Gas (0 = Normal, 1 = Alarm)
R 10279 6 High Limit (0 = Normal, 1 = Alarm)
R 10280 7 Thermostat - Operating aquastat (not fault) (0 = Normal, 1 = Aquastat)
R 10281 8 Manual Override (0 = Normal, 1 = Alarm)
R 10282 9 Flow Switch (0 = Normal, 1 = Alarm)
R 10283 10 No Pilot (0 = Normal, 1 = Alarm)
A-3