63230-216-207/A3 Chapter 5—Setup
9/2002 Configuring the Power Server Communication Connection
19
© 2002 Schneider Electric All Rights Reserved
9. At the C:\ > prompt, enter: nwsetup
The PowerLogic Network Setup Application displays in HyperTerminal.
NOTE: Even if the Power Server will not be used in a networked
environment, you must run the Network Setup application at least once
and then type 5 to quit.
10. Set all of the network setup options as described in Table 1.
NOTE: To change any of the options, enter the option number at the
Enter Option prompt and press Enter.
11. Follow the onscreen instructions to change the value.
12. After changing the options verify that all settings are correct.
13. At the Enter Option prompt, type 5 to quit.
The Power Server reboots automatically.
NOTE: It can take approximately five minutes to reboot. If errors occur,
review all configuration settings before exiting HyperTerminal.
14. Exit HyperTerminal.
Table 1: Power Server Setup—HyperTerminal Options
Option Description
Computer Name
The computer name defaults to the MAC Address. We
recommend that you leave the default computer name. If
you must change the name, it must be a unique alpha-
numeric name, limited to 15 characters, no spaces or
special characters.
IP Address 1
Subnet Mask 1
Use IP Address 1 as the primary address to access all the
capabilities of the Power Server.
Subnet Mask 1 is assigned to IP Address 1.
IP Address 2
Subnet Mask 2
(optional)
IP Address 2 and Subnet Mask 2 are optional. They should
only be used if slave Modbus/Jbus and PowerLogic devices
need to have the same address on both COM 3 and COM 4.
Router Address
Address of your company’s Ethernet LAN router, if
applicable.
MAC Address Unique media access control number (cannot be changed).