SMC Networks SMC 6000A Power Supply User Manual


 
SMA Technologie AG Installation
Installation Guide SMC50A_60A-IEN073320 Page 19
3 If several Sunny Mini Central units are installed in areas where
high ambient temperatures are to be expected, the individual
Sunny Mini Central units must be far enough apart to ensure that
the individual Sunny Mini Central units do not intake the cooling
air of the neighboring unit.
If necessary, increase the clearances and ensure that the device is
sufficiently ventilated!
4 The Sunny Mini Central is accessible at any time (e.g. not mounted
on roofs that are difficult to access).
5 The Sunny Mini Central can be removed from the installation
location easily (by two people), in spite of its weight of 63 kg.
6 The Sunny Mini Central is not installed in areas
where highly flammable materials are stored
or in potentially explosive areas.
7 The Sunny Mini Central is not exposed to direct sunlight, in order
to avoid yield losses of the PV system.
8 The ambient temperature is always between -25 °C and +60 °C.
9 The Sunny Mini Central must be mounted such
that the inverter cannot be touched
inadvertently!
The temperature of individual parts of the
housing and of components inside the Sunny
Mini Central can reach more than 60 °C.
Touching these parts could result in severe
burns.
10
The Sunny Mini Central is installed in such a
way that it is not possible (e.g. for children) to
unintentionally unplug the DC plug connector.
Unintentionally pulling out the DC plug
connectors under load can damage the plugs
and could result in personal injury!
No. Checkpoint Control