SMC Networks SMC 6000A Power Supply User Manual


 
SMA Technologie AG Technical Data
Installation Guide SMC50A_60A-IEN073320 Page 87
14.4.2 Parameter Settings for Germany
Grayed out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany.
Name Short
descr.
Value range Default setting
SMC 5000A SMC 6000A
ACVtgRPro V 230 ... 300 253 253
AntiIsland-
Ampl *
grd 0 ... 10 0 0
AntiIsland-
Freq *
mHz 0.1 ... 2000 500 500
Betriebsart MPP, Ikonst, Stop,
Turbine Mode,
U-konst, Off_grid
MPP MPP
Control Auto, Grid,
Bridge
Auto Auto
Default * GER/VDE0126-1-1,
GB/G83,
AUS/AS4777,
USA/UL1741,
IT/DK5950,
Off_Grid,
SP/RD1663,
Other, trimmed
GER/VDE0126-1-1 GER/VDE0126-1-1
dFac-MAX * Hz/s 0.1 ... 4.0 4 4
dZac-MAX * mOhm 0.35 ... 20000 685 670
E_Total kWh 0 ... 200000 0 0
Fac-delta- * Hz 0.1 ... 4.5 2.45 2.45
Fac-delta+ * Hz 0.1 ... 4.5 0.19 0.19
Fac-Limit delta Hz 0 ... 5 2 2
Fac-Start delta Hz 0 ... 5 1 1
Fan test 0 ... 1 0 0
h_Total h 0 ... 200000 0 0
Inst.-Code
I-NiTest * mA 0 ... 25000 16000 16000