Toshiba 1600EP Power Supply User Manual


 
1600EP Single Phase Uninterruptible Power Supply Systems
Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
Page 3 of 8
6.0 UPS Output
Voltage: 240/208/120 VAC Single Phase
Capacity: kVA kW (@ 0.85PF)
3.6 kVA 3.1 kW
6.0 kVA 5.1 kW
8.0 kVA 6.8 kW
10.0 kVA 8.5 kW
14.0 kVA 11.9 kW
18.0 kVA 15.3 kW
22.0 kVA 18.7 kW
Regulation: +/-3% (with AC power and during battery backup)
Distortion: Less than 6% THD at Full Non-Linear Load
Less than 3% THD at full Linear Load
Step Load: ± 8 % max from 100% to 0 % or from 0% to 100 % linear load
Output Current: kVA
RMS PEAK
3.6 15.0A 45.0A
6.0 25.0A 75.0A
8.0 33.3A 100.0A
10.0 41.6A 125.0A
14.0 58.0A 174.0A
18.0 75.0A 225.0A
22.0 91.6A 275.0A
Overload Capacity (Inverter): 150% for 10 seconds
125% for 30 seconds
1000% for 1 cycle
Crest Factor: 3.0
Frequency: 50/60Hz Auto Sensing
Regulation: ± 0.5Hz / ±1.0Hz / ±1.5Hz (authorized service center selectable only)
Synchronous Range: +/- 1 Hz
Wave Form: Sine wave, Zero Transfer Time
Load Power Factor: 0.85 lagging (0.6 to 1.0)
Efficiency AC to AC: Greater than 83%