Toshiba 1600EP Power Supply User Manual


 
1600EP Single Phase Uninterruptible Power Supply Systems
Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
Page 4 of 8
Noise Isolation: Neutral is bonded to ground on the output of the Isolation transformer
for isolation of common mode
Bypass: Manual bypass provided with switch with less than 4 ms transfer
7.0 UPS Battery
Battery Bus Volts:
3.6 kVA 216 VDC nominal
6.0 kVA 216 VDC nominal
8.0 kVA 288 VDC nominal
10.0 kVA 288 VDC nominal
14.0 kVA 288 VDC nominal
18.0 kVA 288 VDC nominal
22.0 kVA 288 VDC nominal
Backup time: 0.7PF 0.85PF
3.6 kVA 14 minutes 10 minutes
6.0 kVA 7 minutes 7 minutes
8.0 kVA 7 minutes 7 minutes
10.0 kVA 5 minutes 5 minutes
14.0 kVA 7 minutes 7 minutes
18.0 kVA 5 minutes 5 minutes
22.0 kVA 5 minutes 5 minutes
Type of Battery: Enersys NPX-35 Flame Retardant Lead Acid 9Ah/12V
Number of Battery: Six batteries in each pack
Average Recharge: 24 hours (12 hours for 90%)
Battery Voltage Range:
3.6 kVA 170 – 245.7 VDC
6.0 kVA 170 245.7 VDC
8.0 kVA 227 - 327 VDC
10.0 kVA 227 - 327 VDC
14.0 kVA 227 - 327 VDC
18.0 kVA 227 - 327 VDC
22.0 kVA 227 - 327 VDC
Cutoff Voltage: 1.6 Volts per cell
Heat Generation kVA
BTU / Hour
3.6 1588
6.0 2610
8.0 3482
10.0 4352
14.0 6092
18.0 7832
22.0 9600