Toshiba 1600EP Power Supply User Manual


 
1600EP Single Phase Uninterruptible Power Supply Systems
Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
Page 5 of 8
8.0 System Status and Control Indicators
8.1 Panel
The UPS shall have a panel on the front for complete monitoring control of UPS.
Operation panel features:
1) Run/Stop button
2) AC input voltage indicator
3) Inverter status indicator
4) Alarm indicator
5) Fault indicator
6) Liquid Crystal Display (LCD)
The UPS shall have menu driven LCD that displays operating conditions, warning
messages and fault indication messages for the unit.
Operating Conditions Display:
1) Input voltage
2) Output voltage
3) Input frequency
4) Output frequency
5) Output current
6) Battery voltage
7) Battery test results
8) Output voltage adjustment
9) UPS ON/OFF Line
Warning messages:
1) Overload
2) Current limit
3) Emergency power off
4) Battery discharge
5) Battery Low
6) Input undervoltage
7) Battery not good
Fault Messages:
1) DC undervoltage
2) DC overcurrent
3) DC overvoltage
4) Overheat
5) UPS overload
6) Inverter undervoltage
7) Inverter overvoltage