1600EP Single Phase Uninterruptible Power Supply Systems
Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
Page 6 of 8
9.0 Dimensions
3.6 kVA
6.0 kVA 8.0 - 10 kVA 14 - 22kVA
Weight 322 lbs 346 lbs 476 lbs 784 lbs
Depth 28” 28” 28” 39"
Width 10” 10” 13” 18"
Height 33” 33” 34” 35"
Casters and leveling feet are standard
10.0 Communications
10.1 Dry Contact Communication
The remote interface is a standard feature. Signals are available through a DB9 male
connector.
1) AC input present
2) Battery operation
3) Inverter
4) Bypass active
5) Fault
6) Loss of utility
10.2 RS-232C Communication
The RS-232C serial communication interface is available through a DB9 female
connector. The interface allows control of the UPS from a personal computer running
special Toshiba software.
10.3 EPO Control
The UPS shall come with terminals on its rear side for receiving an Emergency Power
Off (EPO) and Remote Run/Stop command from a remote locations.
11.0 Reliability
Demonstrated mean time between failures (MTBF) of 200,000 hours.
12.0 Environment Operation
Operating Ambient Temperature: 0 ~ 40
o
C (32 ~ 104
o
F)
Recommended Temperature: +15oC ~ 25oC
Storage Temperature: -20oC ~ 40oC
Humidity: 30-90%, Non-Condensing
Audible Noise: 50dB (A) maximum @ 1 meter from Front Panel