Toshiba 1600EP Power Supply User Manual


 
1600EP Single Phase Uninterruptible Power Supply Systems
Guide Specifications
3.6, 6.0, 8.0, 10.0, 14.0, 18.0, 22 kVA
Page 7 of 8
Altitude: 3300 ft (1,000 m) above sea level
13.0 Conformance
UL, CUL, ISO 9001, NEMA/PEI-1993
14.0 Warranty
Toshiba Standard warranty includes 3 Years of on site service which covers electronics
and labor, and a 5 year warranty on the batteries (2 years full, 3 years pro-rated)
15.0 Options
15.1 Matching Battery Cabinets
Toshiba UPS offers two matching battery cabinets. Battery runtime may vary based
upon: environmental conditions and percentage of load.
kVA Battery Cabinet Additional Runtime
3.6 UE31-BC-0650 70 minutes
6.0 UE31-BC-0650 50 minutes
8.0 UE31-BC-1825 75 minutes
10.0 UE31-BC-1825 50 minutes
14.0 UE31-BC-1825 35 minutes
18.0 UE31-BC-1825 25 minutes
22.0 UE31-BC-1825 15 minutes
15.2 Line Cords & Receptacle Panels
To meet diverse electrical distribution requirements, Toshiba provides a wide variety of
line cords and receptacle panels to connect various loads to the UPS System.
Line Cord
kVA
Line Cord Description
3.6 UE31-6LC-30A L6-30 Plug with 8" Input Line Cord (3 wire)
6.0 UE31-6LC-50A L6-50 Plug with 8" Input Line Cord (3 wire)
8.0 UE31-8LC-50A L6-50 Plug with 8" Input Line Cord (3 wire)
Receptacles Panel
kVA
Receptacles Description
3.6 ~ 6.0 UE3-RP-B3 Four L6-30R, Two 5-15R (Duplex)
3.6 ~ 6.0 UE3-RP-B5 Five 5-20R (Duplex)
3.6~ 6.0 UE3-RP-B7 Two L6-30R, Four 5-15R (Duplex)
8.0 UE3-RP-C5 Five 5-20R (Duplex)
8.0 UE3-RP-C7 Two L6-30R, Four 5-15R (Duplex)
15.3 UPS Built-in Maintenance Bypass
Every Toshiba UPS system includes a thyristor static bypass switch. For applications
that require complete isolation of input and output power from UPS system, to allow
service personnel to perform routine maintenance and testing without power interruption