8. Transportation
Avoid vibration or shock exceeding 0.5 G to the UPS.
Failing to observe this precaution may cause damage to the unit.
Do NOT expose the UPS to water.
Exposing the UPS to water may damage or deteriorate the UPS.
The UPS is packed in a crate to bear external force well during transportation. However, the following
points should be observed.
(1) Avoid impact or vibration against the UPS during transportation.
(2) Be sure that the water does not directly reach the UPS.
When transporting the UPS by using a crane, follow the specified
procedure and keep the suspension wire angle within 60°
°°
°.
Moving the UPS by any method other than the specified may cause
personal injury by being crushed or trapped by the UPS when it falls or
overturns.
When transporting the UPS by a crane or a forklift truck follow the instructions below.
8.1 Transportation by a crane
Make sure that the suspension wires are hooked at eyebolts on top as shown in Fig 8.1. Keep the
angle within 60° between wires. Wires should be wei ght-rated with the same length. Refer to chapter 7
“Dimension and Weight” for UPS cabinet weight.
Figure 8.1 - Wires and eyebolts to lift the UPS.
CAUTION
WARNING
Less than
60deg