10.3 Anchor bolts
Tighten the anchor bolts to secure the UPS on the floor. Tightening detail is shown in Figure 10.2.
Anchor bolts of 12mm (1/2”) diameter are to be used, clearance holes of 16mm (5/8”) diameter are provided
in the UPS base.
Figure 10.3 - Hole locations and dimensions for anchor bolts.
4 of 16mm-diameter
(5/8
”
) screw holes
Anchor Bolt
4 screw holes
(Side View)
Figure 10.2 -
Anchor bolt tightening
Front
Back
4 x 12mm-Dia.(1/2”)
550mm
(21” 21/32)
100/125kVA: 1,050mm (41” 11/32)
150/180/225kVA: 1,170mm (46” 1/16)
< 100~225kVA >
575mm
(22
”
5/8)
575mm
(22
”
5/8)
564mm
(22
”
3/16)
650mm
(25
”
19/32)
< 250/300kVA >
8 x 12mm-Dia.(1/2”)