Toshiba XLTR-200 Network Card User Manual


 
66
Parameter
Bit Function Bank Mask Adjustment Range Multiplier
0012 high
byte
2nd past trip 0 7F00
low
byte
1st past trip (oldest) 007F
0013 word Pre-compensation output
frequency
0 FFFF
0000 9C40
(0.00 400.00 Hz)
0.01
0014 word Post-compensation output
frequency
0 FFFF
0000 9C40
(0.00 400.00 Hz)
0.01
0015 word Torque current monitor 0 FFFF (Note 2) 0.01
0016 low
byte
Excitation current monitor 0 00FF
00 FF (0 ~ 255%)
1
high
byte
Reserved
0017 word PID feedback value 0 FFFF (Note 2) 0.02
0018 word Motor overload ratio 0 FFFF 0 ~ 65535 100/65535
0019 word Inverter overload ratio 0 FFFF 0 ~ 65535 100/65535
001A word DBR overload ratio 0 FFFF 0 ~ 65535 100/65535
001B word Input power (%) 0 FFFF 0 ~ 6553.5 0.1
001C word Input power (kW) 0 FFFF (Note 3)
001D word Output power (%) 0 FFFF (Note 2) 0.1
001E word Output power (kW) 0 FFFF (Note 2, Note 3)
001F word RR input 0 FFFF 0 ~ 65535 100/65535
0020
Reserved
0021
Reserved
0022
Reserved
0023 low
byte
Inverter typeform monitor 0 00FF Refer to Table 8 (page
68)
8 Input / output power units 0 0100 0: 0.01kW
1: 0.1kW
9,A Command mode status 0 0600 00: terminal
01: panel
10: option
11: RS232C
B,C Frequency mode selection
status
0 1800 00: terminal
01: panel
10: option
11: RS232C
D,E,F Reserved
0024
Reserved
0025 word Output current (amps)
FFFF 0.0 ~ 6553.5 A 0.1
(Note 1).... These monitor voltage units are not affected by the setting of VOLTAGE UNITS SELECTION in
GROUP:UTILITY PARAMETERS; they are always in units of %.
(Note 2).... These parameters use signed data (data values larger than 7FFFH are negative). If the parameter data is
8000H or larger, the actual value can be obtained by: actual value = - [FFFFH - (parameter data) + 1].
(Note 3).... If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is 0.01.
If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier is 0.1.
These values are automatically set according to the inverter’s capacity.