Toshiba XLTR-200 Network Card User Manual


 
79
13.7.9 Protection Function Parameters
Parameter Function / Title Bank Mask Adjustment Range Multiplier
011F
DYNAMIC BRAKING
SELECTION
0 / 1 0003 0000: no dynamic braking (0)
0001: with dynamic braking, no DBR
overload trip (1)
0003: with dynamic braking and DBR
overload trip (2)
0120
BRAKING
RESISTOR VALUE
0 / 1 FFFF
000A 2710 (1.0 1000)
0.1
0121
2
BRAKING
RESISTOR POWER
RATING
0 / 1 FFFF
0001 EA60 (0.01 600.00)
0.01
0122
OVERVOLTAGE STALL
PROTECTION
0 / 1 0004 0000: ON (0)
0004: OFF (1)
0123
DC INJECTION START
FREQUENCY
0 / 1 FFFF
0000 2EE0 (0.00 120.00)
0.01
0124
DC INJECTION
CURRENT
MAGNITUDE
0 / 1 00FF
0000 0064 (0 100)
1
0125
Other
than
0
DC INJECTION
TIME
0 / 1 00FF
0000 0064 (0.0 10.0)
0.1
0126
FWD/REV DC
INJECTION PRIORITY
CTRL
0 / 1 0040 0000: OFF (0)
0040: ON (1)
0127
MOTOR SHAFT
STATIONARY CTRL
0 / 1 0080 0000: OFF (0)
0080: ON (1)
0128
EMERGENCY OFF MODE
SELECTION
0 / 1 0030 0000: Coast stop (0)
0010: Decelerated stop (1)
0020: DC injection stop (2)
0129
2
EMERGENCY OFF
DC INJECTION
TIME
0 / 1 00FF
0000 0064 (0.0 10.0)
0.1
012A
NUMBER OF RETRY
ATTEMPTS
0 / 1 00FF
0000 000A (0 10)
1
012B Other
than
0
TIME BETWEEN
RETRY
ATTEMPTS
0 / 1 00FF
0000 0064 (0.0 10.0)
0.1
012C
REGENERATION POWER
RIDE-THROUGH
0 / 1 0008 0000: OFF (0)
0008: ON (1)
012D
1
REGENERATION
RIDE-THROUGH
TIME
0 / 1 00FF
0000 00FA (0.0 25.0)
0.1
012E
AUTO-RESTART (MOTOR
SPEED SEARCH)
0 / 1 0018 0000: OFF (0)
0008: On power failure (1)
0010: On ST make/break (2)
0018: Both (1) and (2) (3)
012F
ELECTRONIC THERMAL
PROTECT LVL #1
0 / 1 00FF
000A 0064 (10 100)
1
0130
OVERLOAD REDUCTION
START FREQ
0 / 1 FFFF
0000 0BB8 (0.00 30.00)
0.01
0131
MOTOR 150% OVERLOAD
TIME LIMIT
0 / 1 00FF
0001 00F0 (10 2400)
10
0132
OVERLOAD SELECTION
0 / 1 0030 0000: with motor overload trip,
without soft-stall (0)
0010: with motor overload trip and
soft-stall (1)
0020: without soft-stall or motor
overload trip (2)
0030: with soft-stall, without motor
overload trip (3)