13.7.3 Fundamental Parameters #1
Parameter Function / Title Bank Mask Adjustment Range Multiplier
0026
MAXIMUM OUTPUT
FREQUENCY (*)
0 / 1 FFFF
0BB8 9C40 (30.00400.00)
0.01
0027
BASE FREQUENCY #1
0 / 1 FFFF
09C4 9C40 (25.00400.00)
0.01
0028
BASE FREQUENCY
VOLTAGE SELECT (*)
0 / 1 0030 0000: Input voltage level (0)
0020: Automatic setting (1)
0030: Stationary setting (2)
0029
MAXIMUM OUTPUT
VOLTAGE #1
0 / 1 FFFF
0000 0258 (0 600)
1
002A
REVERSE OPERATION
DISABLE SELECT
0 / 1 0020 0000: Reverse allowed (0)
0020: Reverse not allowed (1)
002B
UPPER LIMIT FREQUENCY
0 / 1 FFFF 0000 ~ Fmax 0.01
002C
LOWER LIMIT FREQUENCY
0 / 1 FFFF
0000 UL, Fmax
0.01
002D
VOLTS PER HERTZ
PATTERN (*)
0 / 1 000F 0000: Constant torque (1)
0001: Variable torque (2)
0002: Auto. torque boost (3)
0006: #3 w/ auto. energy savings (4)
000A: Vector control (5)
000E: #5 w/ auto. energy savings (6)
002E
1, 2
VOLTAGE BOOST
#1
0 / 1 FFFF
0000 012C (0.0 30.0)
0.1
002F
ACCELERATION TIME #1
0 / 1 FFFF
0001 EA60 (0.01~ 600.00)
0001 EA60 (0.1~ 6000.0)
0.01
0.1
0030
DECELERATION TIME #1
0 / 1 FFFF
0001 EA60 (0.01~ 600.00)
0001 EA60 (0.1~ 6000.0)
0.01
0.1
0031
ACC/DEC PATTERN #1
SELECTION
0 / 1 0030 0000: Linear (0)
0010: Self-adjusting (1)
0020: S-Pattern #1 (2)
0030: S-Pattern #2 (3)
0032
ACCEL/DECEL PATTERN
ADJUST LOW
0 / 1 00FF
0003 ~ 00FD (0 50) (Note 1)
1
0033
ACCEL/DECEL PATTERN
ADJUST HIGH
0 / 1 00FF
0003 ~ 00FD (0 50) (Note 1)
1
Note 1: Parameter data = (desired setting x 5 + 3), converted to hexadecimal