Trane TR200 Computer Drive User Manual


 
Example of a simple set-up of BACnet
This example shows the necessary steps to set up the TR200 BACnet interface with the following system re-
quirements:
MS/TP running at 38,400 baud
MAC address 20 for the TR200
BACnet Device Instance 0 1025
Highest number of a master stack is 35
Start/stop of drive from BACnet only
Reference from BACnet
Read status of drive (actual speed)
Set the following parameters:
Name Par. number Value
Protocol 8-30 Drive option [9]
Address 8-31 20
Drive Port Baud Rate 8-32 38,400 Baud [4]
Coasting Select 8-50 Bus [1]
BACnet device instance 8-70 1025
MS/TP Max Masters 8-72 35
After the parameters have been set according to the table above, the drive has to be unpowered and repowered
before the changes take effect. When the adjustable frequency drive is detected by the BMS, the drive can be
controlled by BV:1, which will start the motor if set to [1]. Setting AV:0 will set the speed reference of the drive.
The actual speed can be monitored via AV:1. See also
Analog Input and Output Objects
section.
How to Configure the System
TR200 BACnet 4-3