Object
ID
Object Name
Read /
Write
Change-
able De-
scription
Non-vola-
tile RAM
Store
Drive Par.
Alarm
notifi-
cation
Triggers Bus
Timeout
BV:40 Brake Check R No NA 16-90/00 Yes
BV:41 Pwr. Card Temp R No NA 16-90/01 Yes
BV:42 Ground Fault R No NA 16-90/02 Yes
BV:43 Ctrl.Card Temp R No NA 16-90/03 Yes
BV:44 Ctrl. Word TO R No NA 16-90/04 Yes
BV:45 Overcurrent R No NA 16-90/05 Yes
BV:46 Torque Limit R No NA 16-90/06 Yes
BV:47 Motor TH Over R No NA 16-90/07 Yes
BV:48 Motor TH Over R No NA 16-90/08 Yes
BV:49 Inverter Overld. R No NA 16-90/09 Yes
BV:50 DC undervolt R No NA 16-90/10 Yes
BV:51 DC overvolt R No NA 16-90/11 Yes
BV:52 Short Circuit R No NA 16-90/12 Yes
BV:53 Soft-charge fault R No NA 16-90/13 Yes
BV:54 Line Power Fault R No NA 16-90/14 Yes
BV:55 AMA Not OK R No NA 16-90/15 Yes
BV:56 Live Zero Error R No NA 16-90/16 Yes
BV:57 Internal Fault R No NA 16-90/17 Yes
BV:58 Brake Overload R No NA 16-90/18 Yes
BV:59 U Phase Loss R No NA 16-90/19 Yes
BV:60 V Phase Loss R No NA 16-90/20 Yes
BV:61 W Phase Loss R No NA 16-90/21 Yes
BV:62
Serial Communi-
cation Bus Fault
R No NA 16-90/22 Yes
BV:63 24 V Supply Low R No NA 16-90/23 Yes
BV:64 Line Power Fault R No NA 16-90/24 Yes
BV:65 1.8 V Supply Low R No NA 16-90/25 Yes
BV:66 Brake Failure R No NA 16-90/26 Yes
BV:67 Brake IGBT R No NA 16-90/27 Yes
BV:68 Option Changed R No NA 16-90/28 Yes
BV:69 Drive Initialized R No NA 16-90/29 Yes
BV:70 Safe Stop R No NA 16-90/30 Yes
BV:71 Brake Low R No NA 16-90/31 Yes
BV:72
Service Trip P
1691/0
R No NA 16-91/00 Yes
BV:73
Service Trip P
1691/1
R No NA 16-91/01 Yes
BV:74
Service Trip P
1691/2
R No NA 16-91/02 Yes
BV:75
Service Trip P
1691/3
R No NA 16-91/03 Yes
BV:76
Service Trip P
1691/4
R No NA 16-91/04 Yes
BV:77 No Flow R No NA 16-91/05 Yes
BV:78 Dry Pump R No NA 16-91/06 Yes
BV:79 Curve End R No NA 16-91/07 Yes
Table 5. 9: Binary values cont.
How to Control the Adjustable Frequency
Drive
TR200 BACnet 5-9