Trane TR200 Computer Drive User Manual


 
8-35 Minimum Response Delay
Range: Function:
10. ms* [5. - 10000. ms] Specify the minimum delay time between receiving a request and trans-
mitting a response. This is used for overcoming modem turnaround
delays.
8-36 Max Response Delay
Range: Function:
10001.
ms*
[11. - 10001. ms] Specify the maximum permissible delay time between transmitting a re-
quest and receiving a response. Exceeding this delay time will cause
control word timeout.
8-37 Max Inter-Char Delay
Range: Function:
25.00
ms*
[0.00 - 35.00 ms] Specify the maximum permissible time interval between receiving two
bytes. This parameter activates timeout if transmission is interrupted.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input)
and/or via the bus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or serial
communication option.
[2] Logic AND Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] * Logic OR Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via
the serial communication bus.
[0] Digital input Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communication port or serial
communication option.
[2] Logic AND Activates Start command via the serial communication bus/serial com-
munication port, AND additionally via one of the digital inputs.
[3] * Logic OR Activates Start command via the serial communication bus/serial com-
munication port OR via one of the digital inputs.
NOTE: This parameter is active only when par.8-01
Control Site is set to [0]
Digital and control word
.
Parameters
6-6 TR200 BACnet