Trane TR200 Computer Drive User Manual


 
device may have. Please see separate manual
TR200 MetasysMG.
12.NX.YY
.
[4]
[9] FC Option To be used when a gateway is connected to the integrated RS 485 port,
e.g., the BACnet gateway.
The following changes will take place:
-The address for the adjustable frequency drive port will be set to 1 and
par.8-31
Address, is now used to set the address for the gateway on the
network, e.g., BACnet.
-Baud rate for the Drive port will be set to a fixed value (115,200 Baud)
and par.8-32
Baud Rate is now used to set the baud rate for the network
port (e.g., BACnet) on the gateway.
[20]
NOTE: Further details can be found in the Metasys manual.
8-31 Address
Range: Function:
1. N/A* [1. - 126. N/A] Enter the address for the adjustable frequency drive (standard) port.
Valid range: 1–126.
8-32 Baud Rate
Option: Function:
Baud rate selection depends on Protocol selection in par.8-30
Protocol.
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] * 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option: Function:
Parity and Stop Bits for the protocol par.8-30
Protocol using the Adjust-
able Frequency Drive Port. For some of the protocols, not all options will
be visible. Default depends on the protocol selected.
[0] * Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
Parameters
TR200 BACnet 6-5