Tripp Lite 3U Power Supply User Manual


 
10
Storage and Service
Storage
Before storing your UPS, place it in the OFF mode by reversing the Connection procedure: use the POWER button to
place the UPS in STANDBY mode; unplug the UPS; set the double-pole input breaker to the "OFF" position; disconnect
the external battery pack. If you store your UPS for an extended period of time, recharge the UPS batteries once every
three months by following Steps 1, 2 and 3 in the Connection section and allowing the UPS to charge its batteries for 4-6
hours before placing it back in storage. If you leave your UPS batteries discharged for an extended period of time, they
will suffer a permanent loss of capacity.
Service
If returning your UPS for service, contact your local Tripp Lite dealer or distributor. They will refer you to a service center.
Please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter
describing the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.
SMART5000RT3U SMART5000RT3U
with 30A plug* with 50A plug*
Series # (Power Module): AGSM5000Y3U31 AGSM5000Y3U31
Series # (Battery Pack): AGBP4860Y3U AGBP4860Y3U
Output Capacity (VA/Watts): 4475(@208+120V)/4000 5000(@208V), 4800(@120V)/4000
Battery Runtime in Minutes (Half Load/Full Load): 38+/16+** 38+/16+**
Battery Recharge Time: 2-4 hrs.** 2-4 hrs.**
Approvals: UL, cUL, NOM UL, cUL, NOM
* The SMART5000RT3U features a 30A plug. A trained technician may replace it with an user-supplied 50Aplug.
** Battery Runtime listed assumes connection to a single BP48V60RT3U external battery pack. Battery Runtime can be increased with additional external battery packs. Adding external battery packs will also
increase recharge time.
Input Voltage (208V); Input Frequency (60 Hz); Online Input Voltage Range (151-260 volts); Voltage-Regulated Output Voltage Range (208/120V ±9%); On-Battery Output Voltage Range (208/120V ± 5%);
Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode (sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Surge
Protection Modes (H to N, H to G, N to G); Compatible Battery Packs (BP48V60RT3U).
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class Adigital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Note on Labeling
Two symbols are used on the label.
V~ : AC Voltage
V : DC Voltage
Specifications