Tripp Lite 6kVA Power Supply User Manual


 
25
Specifications
The models listed below include a power module, one or two battery modules, and a transformer module. All models include all three
types of modules, with the exception of hardwired (HV) models, which do not include transformer modules. Depending on the model
ordered, the included battery module may be either expandable or nonexpandable. However, if extended runtime is required, all power mod-
ules are fully compatible with expandable Tripp Lite battery modules (Tripp Lite Model # BP240V10RT-3U, sold separately)
Model Information
Model #(s) SU5000RT3UHV* & SU5000RT3U SU6000RT3UHV* & SU6000RT3U SU6000RT3UXR SU10KRT3UHV* & SU10KRT3U
Package Includes:
Power Module (model: SU5000RT3UPM; (model: SU6000RT3UPM; (model: SU6000RT3UPM; (model: SU10KRT3UPM;
series: AGPS5124) series: AGSU60003U) series: AGSU60003U) series: AGSU100003U)
Battery Module #1 (model: BP240V5RT2U; (model: BP240V7RT3U; (model: BP240V10RT-3U; (model: BP240V10RT-3U;
series: AGBP5161) series: AGBP240V7RT3U) series: AGBP240V7RT3U) series: AGBP240V7RT3U)
Non-expandable Non-expandable Non-expandable EXPANDABLE
Battery Module #2 N/A N/A (model: BP240V7RT3U; N/A
series: AGBP240V7RT3U)
EXPANDABLE
Transformer Module (model: SU5000XFMRT2U; (model: SU6000XFMRRT3U; (model: SU6000XFMRRT3U; (model: SU10KXFMRRT3U;
series: AGAC5125) series: AGSM6000SDRT3U) series: AGSM6000SDRT3U) series: AGSM10KSDRT3U)
Approvals: All power modules (UL, cUL, NOM, CE, GOST, SASO, IRAM, FCC Class A). All battery modules except BP240V5RT2U (UL, cUL, NOM). All transformer modules (UL,
cUL, NOM, FCC Class A) * Transformer module not included with hardwired (HV) models.
Input
Input Connection Type 10 ft. cord with L6-30P plug Hardwire Hardwire Hardwire
Input Voltage Range 156V~276V Single Phase 156V~276V Single Phase 156V~276V Single Phase 156V~276V Single Phase
Module Input Voltage 200/208/240V AC 200/208/240V AC 200/208/240V AC 200/208/240V AC
Input Frequency 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz
Input Current 20A 22.6A 22.6A 40A
Inrush Current <150A <150A <150A <200A
Power Factor (Full Load) >0.97 >0.97 >0.97 >0.97
Efficiency (Full Load/On-Line) >87% >87% >87% >88%
Power Module Circuit Breaker N/A 40A (2 pole) 40A (2 pole) 63A (2 pole)
Transformer Module Circuit Breaker N/A 40A (2 pole) 40A (2 pole) 63A (2 pole)
Output
VA 5000 6000 6000 10000
Watts (Power Factor: 0.7) 3500 4200 4200 7000
Output Connection Type 4 receptacles on power module Hardwire Hardwire Hardwire
(2 L6-20R and 2 L6-30R) &
12 receptacles on transformer
module (5-15/20R)
Waveform (On-Line) Sinewave Sinewave Sinewave Sinewave
Waveform (On-Battery) Sinewave Sinewave Sinewave Sinewave
Output Voltage (RMS) 120*/200/208/240V AC 100/120/200/208/240V AC 100/120/200/208/240V AC 100/120/200/208/240V AC
Output Frequency 50/60 Hz (± 0.2 Hz on battery) 50/60 Hz (± 0.2 Hz on battery) 50/60 Hz (± 0.2 Hz on battery) 50/60 Hz (± 0.2 Hz on battery)
Voltage Regulation ±3% ±3% ±3% ±3%
Max. Harmonic Distortion
(Linear Full Load) <3% <3% <3% <3%
(Non-Linear Full Load) <6% <6% <6% <6%
Overload Capabilities 102% (continuous) 102% (continuous) 102% (continuous) 102% (continuous)
102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.) 102%~125% (1 min.)
125%~150% (30 sec.) 125%~150% (30 sec.) 125%~150% (30 sec.) 125%~150% (30 sec.)
>150% (Immediate) >150% (Immediate) >150% (Immediate) >150% (Immediate)
Short Circuit Capability 90A 90A* 90A* 160A*
Power Module Circuit Breaker 20A (2 pole) 40A 40A 63A
Transformer Module* Circuit Breaker Four 20A (single pole) 30A (3 pole) 30A (3 pole) 63A (3 pole)
Crest Factor 3:1 3:1 3:1 3:1
* The short circuit capability at 1ø 2W 120V for the SU6000RT3U and SU6000RT3UXR is greater than 180A, and for the SU10KRT3U is greater than 320A.
Operation
On-Line Transfer Time
(Line to Battery, Battery to Line) 0 ms. 0 ms 0 ms 0 ms
Audible Noise (Full Load @ 1 m) <50 dBA <50 dBA <55 dBA <55 dBA
Indicators
Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).
Communications
Includes an RS-232 DB9 female connector, a dry contact DB9 female connector and an accessory slot.
Physical Specifications
Unit Dimensions (H x W x D)
Power Module 5.25 (3U) x 17.5 x 26 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in.
[13.4 x 44.5 x 66 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.]
Transformer Module* 3.5 (2U) x 17.5 x 20.75 in. 5.25 (3U) x 17.5 x 26 in. 5.25 (3U) x 17.5 x 26 in. 5.25 (3U) x 17.5 x 26 in.
[8.9 x 44.5 x 52.7 cm.] [13.4 x 44.5 x 66.1 cm.] [13.4 x 44.5 x 66.1 cm.] [13.4 x 44.5 x 66.1 cm.]
Battery Module #1 3.5 (2U) x 17.5 x 22.50 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in. 5.25 (3U) x 17.5 x 22.5 in.
[8.9 x 44.5 x 52.7 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.] [13.4 x 44.5 x 57.2 cm.]
Battery Module #2 (if applicable) N/A N/A 5.25 (3U) x 17.5 x 22.5 in. N/A
[13.4 x 44.5 x 57.2 cm.]
Shipping Weight
Power Module 58 lb. [27 kg.] 58 lb. [27 kg.] 58 lb. [27 kg.] 68 lb. [31 kg.]
Transformer Module* 60 lb. [28 kg.] 124 lb. [57 kg.] 124 lb. [57 kg.] 124 lb. [57 kg.]
Battery Module #1 138 lb. [63 kg.] 160 lb. [73 kg.] 160 lb. [73 kg.] 160 lb. [73 kg.]
Battery Module #2 (if applicable) N/A N/A 160 lb. [73 kg.] N/A
* Transformer Module not included with hardwire (HV) models.
Optional corded backplate outlet kits available: SUPDM11
(SU6000RT3UHV); SUPDM12 (SU6000RT3U & SU6000RT3UXR);
SUPDM13 (SU6000RT3U & SU6000RT3UXR); SUPDM15
(SU6000RT3U & SU6000RT3UXR); SUPDM16 (SU6000RT3U
and SU6000RT3UXR)