Tripp Lite SU10KRT1X Power Supply User Manual


 
2
1 – Introduction
2 – Important Safety Instructions
Tripp Lite’s SmartOnline Rack/Tower On-Line UPS System with Parallel Redundancy Capability provides long-lasting battery backup for data
centers, telecommunications, networks, industrial facilities, security, emergency systems and other critical applications that require high capacity,
high availability and extended runtime. True on-line operation continuously transforms 3-phase input power into precision-regulated single-phase
output to guarantee maximum equipment protection and stability. Built-in parallel redundancy capability combines up to four UPS systems to
provide increased capacity (up to 40 kVA) and/or fault tolerance.
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the installation, operation and storage of this product.
Failure to comply will invalidate the warranty and may cause serious property damage and/or personal injury.
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring must be performed by a qualified electrician, in accordance with the warnings in this manual and all
applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage.
Location Warnings
• InstalltheUPSsysteminawellventilated,temperature-andhumidity-controlledindoorenvironment,awayfrommoisture,temperature
extremes, flammable liquids and gasses, sparks, smoke, open flames, corrosive materials, conductive contaminants, dust and direct sunlight.
• InstalltheUPSsysteminalevel,structurallysoundlocation.
• TheUPSsystemisextremelyheavy;becarefulwhenmovingtheunit.DonotattempttomovetheUPSsystemwithoutassistance.
• OperatetheUPSsystematambientindoortemperaturesbetween0°Cand40°Conly,withnon-condensinghumiditybetween0%and90%.
Formaximumbatterylifespan,maintainanindoortemperaturebetween15°and25°C.(Batterylifespandecreasesbyhalfforevery10°C
above25°C.)
• LeaveadequatespacearoundallsidesoftheUPSsystemforproperventilation.KeeptherearpaneloftheUPSsystematleast30cmaway
from the wall or any object that may impede the airflow of the UPS system.
• Donotblock,coverorinsertobjectsintotheexternalventilationopeningsoftheUPSsystem,orotherwiseimpedetheairflowfromthefront
to the rear of the UPS system.
• DonotplaceanyobjectontheUPSsystem,especiallycontainersofliquid.Spillingliquidsontheunitordroppingforeignobjectsintotheunit
will invalidate the warranty.
• Installtheunitinalocationwherecontactwithpeopleisminimized.
• Keepallrecordedmagneticmedia,suchasdiskettes,tapesandcartridges,aminimumof60cmfromtheUPSsystem.Themagneticfield
created by the UPS system may erase or corrupt data on those devices.
• Foremergencyuse,installafireextinguisherratedforenergizedelectricalequipmentfires(ClassCratingorexactequivalent,withanon-
conductive extinguishing agent) near the UPS system.
• Donotmountunitwithitsfrontorrearpanelfacingdown(atanyangle).Mountinginthismannerwillseriouslyinhibittheunit’sinternal
cooling, eventually causing product damage not covered under warranty.
Connection Warnings
• ConnecttheUPSsystemdirectlytoaproperlygrounded,dedicatedACsupplycircuit.Thevoltageofthesupplycircuitshouldmatchtheinput
voltage of the UPS system. Confirm that the utility AC input is correctly grounded.
• TheUPSsystemincludesanEMIfilter.Topreventpotentialleakageofhazardouscurrent,confirmthattheACsupplycircuitissecurelygrounded.
• ConfirmthattheUPSsystemisproperlygroundedbeforeconnectingwiththeutilityACinput.
• TheUPShasitsowninternalenergysource(battery).TheremaybehazardousvoltageattheoutputterminalsevenwhentheUPSsystemis
not connected to AC power.
• DonotattempttopowerpureinductiveorcapacitiveloadswiththeUPSsystem.
• Donotopenthecase.Therearenouser-serviceablepartsinside.Anyrequiredinstallation,serviceorrepairmustbeperformedbyqualified
service personnel.
• IftheUPSsystemreceivespowerfromamotor-poweredACgenerator,thegeneratormustprovideclean,filtered,computer-gradeoutput.
• Toavoidelectricalshock,makesuretheUPSsystemiscompletelyturnedoffwhenmovingitfromoneplacetoanother.
• TheUPSsystemhasanoptional“ConstantVoltage/ConstantFrequency”operationalsetting.Forthecorrectsettingandwiringinformation,
contact Tripp Lite.
• DisconnecttheUPSsystemcompletelyfromtheACsupplycircuitbeforeservicingtheUPSsystem.Incorporateaneasilyaccessible
disconnect device in the fixed wiring.