Westinghouse MA7200 Plus Power Supply User Manual


 
MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
________________________________________________________________
TECO – Westinghouse Motor Company
17
To further cover the PID Sleep function, the following is an example of the various
parameter settings that could be used. In this example the system will have the following
specifications:
- Max. Pump Motor Speed : 3600 RPM.
- Set Point: 150 PSI.
- Feedback Transducer Range: 0 – 200 PSI.
- Pump System Sleep Level: 2160RPM or 60% of max. speed set by
(P21-01=060.00). Sleep Level Delay Time: 10 sec. set by (P2-02=010.0 ).
- Pump System Wakeup Level: 100 PSI set by (P2-03=0100). Wakeup Time: 5 sec.
set by (P2-04=005.0).
Referring to Step 9, set the engineering units to PSI (P1-01=02) and then the range to 200
(P1-02=0200).
On the following pages the keypad navigation sequence is shown in setting the PID
parameters.
NOTE: The inverter must be in the Stop mode in order to turn on the sleep function.