Westinghouse MA7200 Plus Power Supply User Manual


 
MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________
________________________________________________________________
TECO – Westinghouse Motor Company
9
Step 8
– Select PID control (Sn-64), and Feedback input (Sn – 24) [4 – 20 mA
or 0 – 10 Vdc]
Before selecting the parameter(s), ensure the inverter is in the STOP mode.
To activate PID control parameter (Sn-64) must be set to =1.
The Feedback Input parameter (Sn –24) is set to = 1 (AIN, 4-20 mA), as factory default. To
select (VIN, 0-10 Vdc), (Sn-24) must be set to 0. (See Figs. 3a, 3b and 3c for feedback
connections)
To set the parameter(s), follow the navigation procedure as shown next.
key twice
Flashing
1 - Press the
2 - Press the
3 - Press the
key until display shows
4 - Press the key
(Turn on PID control)
key
0
key to .
5 - Press the
key
6 - Press the
2 Seconds
7 - Press the
key to return to the main display.
Flashing
1
Flashing
1