Xantrex Technology APG-HPD Power Supply User Manual


 
Release 1.0 11
Section 1. Features and Specifications
Description
The Analog Programming (APG) Interface is an internal option card for analog
programming of XT and HPD Series DC power supplies with a 0-10Vdc
programming source or a 0-10k resistance. A 25-pin female DSUB connector on
the unit's rear panel enables connections to the card.
Features
Programming output voltage and/or current limit using a 0-10Vdc programming
source or a 0-10k resistance. Externally adjustable offset and range.
Fixed programming of output voltage and/or current limit using an available
10V reference (10mA max source)
0-10V readback of output voltage and current with externally adjustable offset
and range
Status signals for programming mode, operating mode, OVP (over voltage
protection) flag, and output fail flag
Adjustable OVP with reset and flag
TTL shutdown with selectable positive or negative logic
Tracking for multiple supplies of the same output
Specifications
Remote Analog Programming 0-10Vdc for 0-100% of rated voltage or current ±0.1%
0-10k for 0-100% of rated voltage or current ±0.1%
OVP Trip Range 3V to full output + 10%
Remote ON/OFF 2 to 25Vdc high. <0.8Vdc low. User-selectable logic
Tracking Accuracy ±1%