Adjusting the C-Series Voltage Settings
975-0004-01-02 Rev D 23
For FLOAT charge voltage, the potentiometer scale is
calibrated follows:
• 12-volt system: 12.5 to 14.5 volts
in increments of 0.2 volts,
• 24-volt system: 25.0 to 29.0 volts
in increments of 0.4 volts, and
• 48-volt system: 50.0 to 58.0 volts
in increments of 0.8 volts.
Figure 2-10
Bulk and Float Charge Settings for Charge/Diversion
Control Mode
15.0
13.0
1
4.0
BULK (CHG
)
13.2
13.4
13.6
13.8
14.2
14.4
14.6
14.8
FLOAT (CHG
)
14.5
12.5
1
3.5
12.7
12.9
13.1
13.3
13.7
13.9
14.1
14.3
30.0
26.0
2
8.0
BULK (CHG
)
26.4
26.8
27.2
27.6
28.4
28.8
29.2
29.6
FLOAT (CHG
)
29.0
25.0
2
7.0
25.4
25.8
26.2
26.6
27.4
27.8
28.2
28.6
60.0
52.0
5
6.0
BULK (CHG
)
52.8
53.6
54.4
55.2
56.8
57.6
58.4
59.2
FLOAT (CHG
)
58.0
50.0
5
4.0
50.8
51.6
52.4
53.2
54.8
55.6
56.4
57.2
12-Volt System Settings
24-Volt System Settings
48-Volt System Settings (C40 only)