Xantrex Technology C40 Power Supply User Manual


 
Operation
58 975-0004-01-02 Rev D
Equalization Mode Indication (Red/green)
Be sure to read all cautions and warning regarding
equalization charging batteries BEFORE allowing an
equalization charge to occur. Damage to batteries can occur.
Alternating Red and Green
The controller is in the EQUALIZE mode.
It will automatically stop the equalization process after
accumulating two hours of operation at a voltage above the
BULK setting.
The user can manually stop the equalization process at any
time by pressing the reset switch until the status LED stops
alternating red and green.
Load Control Indications (Red)
The flashing rate of the LED indicates the controller’s stage
of operation and approximate battery voltage.
Blinking Red
As battery voltage approaches the LVD setting, the LED will
blink red several times (up to five) and then pause providing
an indication of battery voltage. Refer to Table 3-1 to
determine the battery voltage.
Solid Red
The controller is in the Load Control mode and the battery
voltage has reached the Low Voltage Disconnect (LVD)
setting. After a 6-minute delay, DC loads will be
disconnected unless the user reduces the loads to a point that
the battery voltage exceeds the LVD setting.