Xantrex Technology C40 Power Supply User Manual


 
Adjusting the C-Series Voltage Settings
975-0004-01-02 Rev D 25
The scale for the Low Voltage Disconnect setting is
calibrated as follows:
12-volt system: 10.5 to 12.5 volts
in increments of 0.2 volts,
24-volt system: 21.0 to 25.0 volts
in increments of 0.4 volts, and
48-volt system: 42.0 to 50.0 volts
in increments of 0.8 volts.
Figure 2-12
LVR and LVD Settings for Load Control Mode
12-Volt System Settings 24-Volt System Settings
14.0
12.0
1
3.0
L
.
V
.
R
(LOAD)
L
OW
V
OLTAGE
R
ECONNECT
12.2
12.4
12.6
12.8
13.2
13.4
13.6
13.8
12.5
10.5
1
1.5
10.7
10.9
11.1
11.3
11.7
11.9
12.1
12.3
L
.
V
.
D
(LOAD
)
L
OW
V
OLTAG
E
D
ISCONNECT
28.0
24.0
2
6.0
24.4
24.8
25.2
25.6
26.4
26.8
27.2
27.6
25.0
21.0
2
3.0
21.4
21.8
22.2
22.6
23.4
23.8
24.2
24.6
L
.
V
.
R
(LOAD)
L
OW
V
OLTAGE
R
ECONNECT
L
.
V
.
D
(LOAD
)
L
OW
V
OLTAG
E
D
ISCONNECT
56.0
48.0
5
2.0
48.8
49.6
50.4
51.2
52.8
53.6
54.4
55.2
50.0
42.0
4
6.0
42.8
43.6
44.4
45.2
46.8
47.6
48.4
49.2
L
.
V
.
R
(LOAD)
L
OW
V
OLTAGE
R
ECONNECT
L
.
V
.
D
(LOAD
)
L
OW
V
OLTAG
E
D
ISCONNECT
48-Volt System Settings (C40 only)