Xantrex Technology PV100S-208 Power Supply User Manual


 
Operator Interface Controls
152315 Rev C 1–7
Operator Interface Controls
Operator interface controls are located on the front door of the main inverter
enclosure. These controls include an ON/OFF Switch, 4-line LCD display and
keypad called the Universal Frontpanel Control Unit (UFCU). Additionally there
is an AC and DC Disconnect on the AC Interface Enclosure and the DC Interface
Enclosure Doors.
Main Enclosure Door Interlock Switch
The front door of the PV100S main enclosure is equipped with an interlock switch
to preclude operation while the front door is open. Opening the door of the main
inverter enclosure will initiate an immediate controlled shutdown of the PV100S
and opens both the main AC and DC contactors. The main AC and DC contactors
cannot be closed unless the door’s interlock is in the engaged position. The
PV100S is prevented from being restarted until the door is again closed and the
switch is in the engaged position.
It is required that the PV100S main enclosure door must be locked during normal
operation. The door interlock switch does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV100S, follow the
de-energize Lockout and Tag procedure on
page x.
Figure 1-2
PV100S Operator Interface Components
DC Disconnect
Switch
LCD
Display
Universal
Frontpanel
Control
(UFCP)
ON/OFF
Switch
AC Disconnect
Switch
AC Interface Enclosure
(AC Side View)
Main Inverter Enclosure
(Front View)
Communication
Enclosure
DC Interface
Enclosure