Xantrex Technology PV100S-208 Power Supply User Manual


 
Anchoring the PV100S
152315 Rev C 2–13
Anchoring the PV100S
The PV100S is designed to be installed in either an indoor or outdoor location. It
must be placed on and anchored to a level concrete floor or pad. The concrete
floor or pad, upon which the PV100S is anchored, must be structurally designed to
meet any local, state, or national requirements for weight, seismic, and wind sheer
if applicable.
Four 5/8" holes are provided in the feet of the main inverter, and six 5/8" holes are
provided in the feet of the AC interface/transformer assembly for anchoring to the
floor or pad.
Figure 2-9 and Figure 2-10 depict the layout patterns of the anchoring holes for
both the PV100S main inverter and the AC interface/transformer assembly.
Figure 2-9
Main Inverter Anchor Bolt Pattern (Not to scale)
29" (73.7 cm)
16 ¼"
(40.6 cm)
5/8"
(1.5 cm)
(x4)