Xantrex Technology PV100S-208 Power Supply User Manual


 
Planning
2–6 152315 Rev C
Layout Options
The PV100S is shipped as two separate assemblies and can be arranged as shown
in Figure 2-1 or Figure 2-2.
The PV100S can be arranged in a number of different system layout options to fit
specific site requirements. The AC interface/transformer assembly may be
co-located adjacent to the left side of (or behind) the Main Inverter Enclosure up
to, and not exceeding, 15 feet away.
Given the flexibility to co-locate the AC interface/transformer assembly to fit a
desired system layout, the interconnect AC power conductors and conduit
between the Main Inverter Enclosure and the AC interface/transformer assembly
are to be supplied by the installer. See Figure 2-1 and Figure 2-2, depicting two
options for locating the AC interface/transformer assembly adjacent to the main
inverter.
Figure 2-1
PV100S Layout Option A
Transformer
Enclosure
Inverter
Enclosure
DC Interface
Enclosure
AC
Interface
Enclosure
Communications
Enclosure
6" Minimum Clearance
Minimum
Clearance*
(15' Max. Distance
from Inverter)
12"
Conduit
36"
Minimum
Clearance
36"
Minimum
Clearance
12' (3.6 m)
6'
(1.8 m)
36"
Minimum
Clearance
BASE: Concrete Floor or Pad
Approximately 12 ft by 6 ft
(3.6 m x 1.8 m)
Minimum
Clearance
12"
Minimum
Clearance
12"
36"
Minimum
Clearance
Minimum Dimension of Base:
Approximately 12 ft. by 6 ft. (3.6 m x 1.8 m)