Introduction
1–6 152315 Rev C
Environmental Specifications
The following environmental specifications are the same for both models of the
PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Table 1-3
Environmental Specifications
Specification Value
Dimensions
Inverter and DC Interface
Transformer and AC Interface
Overall System Footprint:
Layout Option A
Layout Option B
82 in H x 60 1/4 in W x 22 in D
(208 cm H x 153 cm W x 56 cm)
44 in H x 50 in W x 34 in D
(112 cm H x 127 cm W x 86 cm D)
12 ft W x 6 ft L (approximate)
(3.6 m x 1.8 m)
9 ft W x 7 ft L (approximate)
(2.7 m W x 2.1 m L)
Weight
Inverter and DC Interface
Transformer and AC Interface
Overall Weight
1000 lbs (approximate)
1400 lbs (approximate)
2400 lbs (approximate)
Allowable Ambient Temperature
Operating
Storage
-20 °C to 50 °C Maximum
-40 °C to 50 °C Maximum
Relative Humidity To 95%, Non-condensing
Elevation Power Derated above 6600 ft
Clearance (ventilation and
serviceability)
In front of access doors: 36 in (91 cm)
In front of access panels: 36 in (91 cm)
Sides: 12 in (30 cm)
Back: 6 in (15 cm)
Maximum Distance between Main
Inverter Enclosure and AC
Interface/Transformer Enclosure
15 ft (4.5 m)